Key technical points for using new reverse osmosis (RO) membranes:
1. Thoroughly rinse the quartz sand and coconut-shell activated carbon; newly installed media should be rinsed for an extended period.
2. Test for residual chlorine. If levels exceed the limit, address this issue before proceeding with the RO membrane installation/operation.
3. After installing the new membrane, flush it with water and allow it to soak for 1–2 hours. Since the membranes are supplied in a dry state, soaking ensures they are sufficiently wetted, which helps prevent damage caused by excessive pressure.
4. Start the high-pressure pump, increasing the pressure gradually-from 2 bar (kg/cm²) up to 8–10 bar (kg/cm²)-to optimize the salt rejection performance of the new membrane.
5. Ensure residual chlorine levels are kept below 0.003 mg/L.
6. Open the concentrate (brine) valve before starting the high-pressure pump. Once the pump is running, slowly adjust the concentrate valve to maintain a recovery rate of approximately 15% per membrane element.
7. Discard the permeate (product water) generated during the first 30 minutes of operation, as the membranes contain protective solutions that could otherwise affect the taste of the water.
8. Ensure the pH of the feed water is above 6.5.
Generally, RO membrane elements have a service life of approximately 2–3 years. To extend this lifespan, the membranes can be cleaned-typically through physical flushing or chemical cleaning. When physical flushing is no longer sufficient to restore the membrane's performance, chemical cleaning is required.
Based on operational experience, if an RO system requires cleaning every three months or longer, it is considered acceptable. If cleaning is necessary every 1–3 months, the operating conditions should be improved, and the effectiveness of the pre-treatment process should be enhanced.
Determining the need for cleaning:
(1) The normalized permeate (product water) flow rate has decreased by more than 10%. (2) The normalized salt passage has increased by more than 10%.
(3) To maintain a normal permeate flow rate, the pressure differential between the feed water and the concentrate (after temperature correction) has increased by more than 10%.
(4) The internal components exhibit significant fouling or scaling.
(5) Prior to a long-term shutdown of the RO system.
(6) During routine maintenance of the RO system.
Before deciding to clean a reverse osmosis (RO) system, one should also consider other potential causes for the aforementioned phenomena, such as:
☆ A decrease in operating pressure (due to malfunctions in pressure control devices or issues with the high-pressure pump);
☆ A drop in feed water temperature (due to heater failure or seasonal temperature changes);
☆ An increase in the salt content of the feed water;
☆ Abnormalities in the pretreatment process;
☆ Permeate contamination by concentrate, caused by factors such as membrane damage, misalignment of the center tubes in series-connected membrane elements, or compromised O-ring seals within the pressure vessels.
2. Contaminants
Common contaminants found in RO membrane elements include CaCO3, CaSO4, BaSO4, SrSO4, metal oxides, silica deposits, organic matter, and biological slime. If the antiscalant dosing system or the acid-dosing system malfunctions, CaCO3 may precipitate within the membrane elements; in such cases, chemical cleaning-either via circulation or overnight soaking-should be performed.
3. Cleaning Formulations
Different contaminants cause varying degrees of damage to the membranes, and specific cleaning solutions should be selected based on the type of contaminant present.

4. Cleaning Equipment
(1) RO Cleaning System
Typically consists of a cleaning pump, a chemical mixing tank, a 5–20 μm cartridge filter (security filter), a heater, associated piping and valves, and control instrumentation.
(2) Operation
Cleaning methods include static soaking and circulation cleaning. In static soaking, the membranes are immersed in a cleaning solution for a duration ranging from approximately 1 to 15 hours, depending on the severity of the fouling. The general procedure for circulation cleaning is as follows:
1. Use a pump to feed water (permeate or high-quality water) from the chemical mixing tank into the pressure vessels, and flush the system for several minutes.
2. Prepare the cleaning solution by mixing the appropriate chemicals with water in the chemical mixing tank. 3. Circulate the cleaning solution through the pressure vessel for 1 hour or for the predetermined duration. The cleaning flow rate can be determined according to the table below; in cases of severe fouling, the flow rate may be increased to 150% of the value specified for the membrane elements. Note that this will result in a higher pressure drop; generally, this should be controlled so as not to exceed 0.10–0.14 MPa per membrane element, or 0.4 MPa per membrane assembly. When initiating the cleaning process, introduce the heated cleaning solution into the pressure vessel at 50% of the flow rate specified in the table. Adjust the pressure to a level sufficient to overcome the pressure drop between the feed inlet and the concentrate outlet, while ensuring that no permeate (product water) is produced. To prevent dilution of the cleaning solution, open the concentrate discharge valve to drain any standing water from the system before beginning the cleaning process. Reverse osmosis (RO) systems may be cleaned in stages. The direction of the cleaning flow must be the same as the normal operating flow; reverse-flow cleaning is strictly prohibited, as it may cause the membrane layers to protrude and damage the membrane elements.
4. Once the circulation cleaning is complete, thoroughly clean the chemical dosing/mixing tank using fresh water (permeate).
5. Flush the aforementioned pressure vessels with fresh water.
6. After flushing, operate the RO system with the permeate discharge valve open until the permeate is clean, free of foam, and contains no traces of the cleaning solution-a process that typically takes 15–30 minutes.
Replacement of Reverse Osmosis Membranes
After a period of normal operation, RO membrane elements may become fouled by suspended solids or sparingly soluble salts present in the feed water. Symptoms include:
1. An increase in the weight of the RO membrane elements;
2. A significant change (increase or decrease) in the salt rejection rate of the RO membranes;
3. A noticeable decline in the permeate production rate of the RO system under standard operating pressure;
4. A requirement for higher operating pressure to maintain the target permeate production rate;
5. An increase in the pressure drop between the feed inlet and the concentrate outlet of the RO system;
6. If a membrane element is removed from the pressure vessel and water poured onto its feed-side face fails to flow through the element-spilling instead over the edge-it indicates that the feed channels are blocked. The decision to replace the RO membrane elements should be based on an assessment of the actual conditions.